Facility Level Energy and Cost Analyses for Water Cooled Supercomputer Systems

[+] Author Affiliations
Evan G. Colgan

IBM T. J. Watson Research Center, Yorktown Heights, NY

Madhusudan K. Iyengar

IBM Systems & Technology Group, Poughkeepsie, NY

Paper No. InterPACK2009-89177, pp. 799-806; 8 pages
doi:10.1115/InterPACK2009-89177
From:
  • ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability
  • ASME 2009 InterPACK Conference, Volume 2
  • San Francisco, California, USA, July 19–23, 2009
  • Conference Sponsors: Electronic and Photonic Packaging Division
  • ISBN: 978-0-7918-4360-4 | eISBN: 978-0-7918-3851-8
  • Copyright © 2009 by ASME

abstract

This paper describes the facility level design of future water cooled supercomputers with an emphasis on the energy efficiency opportunities related to the use of water cooled economizer based facility cooling in lieu of traditional refrigeration chiller architectures. A hybrid cooled 80kW server rack with both air and water cooled components is considered for the analyses. In this system, 90% of the rack heat load is rejected directly to pumped water lines via CPU cold plates and conduction cooling and the remaining 10% rack power is rejected to the room ambient air and is subsequently transferred to the water loop via air to liquid heat exchanger based devices. Air to water heat exchangers are not included in the server racks. The facilities cost for water cooling of high power computer racks has been analyzed for data centers situated in two different geographic locations. The study takes into account both the energy savings resulting from the loop design as well as the duration of time for which these savings can be realized at the selected locations. Test data for the water cooled CPU modules is used to project the maximum chip junction temperature for different chilled water temperatures which are in turn determined using the outdoor air temperatures for different times of the year. After calculating the 5 year energy consumption savings over the traditional plant design for each location, for the two different geographic locations in the US considered, it was found that the outdoor weather permitted the use of the economizer based configuration for 53–76% and 60–80% of the time for A and B locations, respectively, yielding per rack energy related savings of $6–21k and $17–26k, respectively, for the thermal conditions considered.

Copyright © 2009 by ASME
Topics: Water

Figures

Tables

Interactive Graphics

Video

Country-Specific Mortality and Growth Failure in Infancy and Yound Children and Association With Material Stature

Use interactive graphics and maps to view and sort country-specific infant and early dhildhood mortality and growth failure data and their association with maternal

NOTE:
Citing articles are presented as examples only. In non-demo SCM6 implementation, integration with CrossRef’s "Cited By" API will populate this tab (http://www.crossref.org/citedby.html).

Some tools below are only available to our subscribers or users with an online account.

Related Content

Customize your page view by dragging and repositioning the boxes below.

Related eBook Content
Topic Collections

Sorry! You do not have access to this content. For assistance or to subscribe, please contact us:

  • TELEPHONE: 1-800-843-2763 (Toll-free in the USA)
  • EMAIL: asmedigitalcollection@asme.org
Sign In